Technical data | KL3464 | KS3464 |
---|---|
Number of inputs | 4 |
Power supply | via the K-bus |
Signal voltage | 0…10 V |
Technology | single-ended |
Internal resistance | > 130 kΩ |
Common-mode voltage UCM | – |
Conversion time | ~ 2 ms |
Resolution | 12 bit |
Measuring error | < ±0.3="" %="" (relative="" to="" full="" scale=""> |
Electrical isolation | 500 V (K-bus/signal voltage) |
Current consumption power contacts | – |
Current consumption K-bus | typ. 100 mA |
Bit width in the process image | input: 4 x 16 bit data (4 x 8 bit control/status optional) |
Configuration | no address or configuration setting |
Special features | – |
Weight | approx. 75 g |
Operating/storage temperature | -25…+60 °C/-40…+85 °C |
Relative humidity | 95 %, no condensation |
Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
Protect. class/installation pos. | IP 20/variable |
Pluggable wiring | for all KSxxxx Bus Terminals |
Approvals | CE, UL, Ex, GL |
8 (029) 555-8-000 | |
8 (044) 555-8-000 | |
8 (017) 255-8-000 |