General specifications | |
---|---|
Signal type | Digital Output |
Functional safety related parameters | |
Safety Integrity Level (SIL) | SIL 3 |
Performance level (PL) | PL e |
Supply | |
Connection | loop powered |
Rated voltage | 19 ... 30 V DC loop powered |
Power dissipation | < 1.5 W |
Power consumption | < 1.5 W |
Input | |
Connection side | control side |
Connection | Input terminals 7, 8 ; test input terminals 9, 10, 11, 12 |
Pulse/Pause ratio | 150 ms / 150 ms |
Test pulse length | max. 4 ms from DO card |
Test input | see Functional Safety Manual |
Signal level | 0-signal: -5 ... 5 V 1-signal: 19 ... 26.5 V |
Rated current | 0-signal: typ. 1.6 mA at 1.5 V DC; typ. 8 mA at 3 V DC (maximum leakage current DO card) 1-signal: ? 36 mA (minimum load current DO card) |
Output | |
Connection side | field side |
Connection | terminals 4, 5, 6 |
Contact loading | 253 V AC/5 A/cos ? 0.7; 30 V DC/5 A resistive load 253 V AC / 1/2 HP |
Minimum switch current | 10 mA / 24 V DC |
Energized/De-energized delay | 150 ms / 150 ms |
Mechanical life | 5 x 106 switching cycles |
Fuse rating | 2.5 A (scope of delivery) max. 5 AT, recommended maximum utilization of the fuse: 80 % |
Transfer characteristics | |
Switching frequency | < 3 Hz |
Galvanic isolation | |
Input/Output | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
Indicators/settings | |
Display elements | LEDs |
Labeling | space for labeling at the front |
Directive conformity | |
Electromagnetic compatibility | |
Low voltage | |
Machinery Directive | |
Conformity | |
Electromagnetic compatibility | NE 21:2012 , EN 61326-3-1:2008 , EN 61326-3-2:2008 |
Degree of protection | IEC 60529:2013 |
Ambient conditions | |
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) Observe the temperature range limited by derating, see section derating. |
Mechanical specifications | |
Degree of protection | IP20 |
Connection | screw terminals |
Mass | approx. 120 g |
Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2 |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Data for application in connection with hazardous areas | |
Certificate | PF 15 CERT 3933 X |
Directive conformity | |
International approvals | |
UL approval | E106378 |